ecms_neu_mini.png

Digital Library

of the European Council for Modelling and Simulation

 

Title:

Saturation Relay vs. Relay Transient Identification Tests For A TDS Model

Authors:

Libor Pekar, Roman Prokop

Published in:

 

(2013).ECMS 2013 Proceedings edited by: W. Rekdalsbakken, R. T. Bye, H. Zhang  European Council for Modeling and Simulation. doi:10.7148/2013

 

ISBN: 978-0-9564944-6-7

 

27th European Conference on Modelling and Simulation,

Aalesund, Norway, May 27th – 30th, 2013

 

Citation format:

Libor Pekar, Roman Prokop (2013). Saturation Relay vs. Relay Transient Identification Tests For A TDS Model, ECMS 2013 Proceedings edited by: W. Rekdalsbakken, R. T. Bye, H. Zhang, European Council for Modeling and Simulation. doi:10.7148/2013-0446

 

DOI:

http://dx.doi.org/10.7148/2013-0446

Abstract:

The paper brings a comparison of two novel combinations of a relay identification test with a Time Delay System (TDS) model. Namely, the on/off plus saturation relay test and relay transient experiment are introduced. In the former case with more then two unknown model parameters, it is necessary to apply some technique for frequency response multiple-points identification; here, the Autotune Variation Plus (ATV+) procedure introducing an artificial delay is utilized. Limit cycles data are evaluated via an unordinary time-domain approach and using the Discrete Time Fourier Transform (DTFT), respectively. Both methodologies are verified and compared on a model of the circuit heating laboratory system with internal delays.

Full text: